Busbar & Insulators
Height: 35
Outer diameter: 36
Creepage line length: 63 mm
Arbetstemperatur: 250 °C
Dry test voltage: 17 kV
Maximum load according to EN 61373 test conditions: 150 N
Bending strength (flexion): 1600 N
Tensile strength (traction): 6000 N
Compressive breaking load: 10 000 N
Brottmoment vid torsion: 35 Nm
Weight: 75 g
Krypningsavstånd är det geometriska måttet på ytavståndet mellan den övre gängan och den nedre gängan på isolatorn.

Ceramic bearing insulators are the ideal choice for equipment used in highly aggressive environments, typical of industrial areas. Thanks to the inorganic material, the insulator’s surface is insensitive to flashover even in short-term overvoltages. The glazed and smooth surface reduces the adhesion of contaminating dust and makes cleaning easy.
In addition, the ceramic material provides the best properties against fire risk. The economic competitiveness should also be taken into account, especially in comparison with other types of insulators.